EM600 High-Performance Vector Control Inverter User Manual 59 Function Name of Function Parameter Description Unit Default Property Code Code 1: Main Frequency Source A - Auxiliary Frequency Source B 2: The Bigger of Main A and Auxiliary B 3: The Smaller of Main A and Auxiliary B F00.09 Reference Option for Auxiliary Frequency Source B at Main and Auxiliary Arithmetic 0: Relative to Maximum Frequency 1: Relative to Main Frequency Source A 0 〇 F00.10 Main Frequency Source Gain 0.0 - 300.0 % 100.0 ● F00.11 Auxiliary Frequency Source Gain 0.0 - 300.0 % 100.0 ● F00.12 Synthetic Gain of Main and Auxiliary Frequency 0.0 - 300.0 % 100.0 ● F00.13 Analog Quantity Adjustment of Synthetic Frequency 0:
Synthetic Frequency of Main and Auxiliary Channels 1: AI1 * Synthetic Frequency of Main and Auxiliary Channels 2: AI2 * Synthetic Frequency of Main and Auxiliary Channels 3: AI3 * Synthetic Frequency of Main and Auxiliary Channels 4: AI4 * Synthetic Frequency of Main and Auxiliary Channels 5: High-Frequency Pulse (PULSE) * Synthetic Frequency of Main and Auxiliary Channels 0 〇 F00.14 Acceleration Time 1 0.00 - 650.00 (F15.13=0) 0.0 - 6500.0 (F15.13=1) 0 - 65000 (F15.13=2) s 15.00 ● F00.15 Deceleration Time 1 0.00 - 650.00 (F15.13=0) 0.0 - 6500.0 (F15.13=1) 0 - 65000 (F15.13=2) s 15.00 ● F00.16 Maximum Frequency 1.00 - 600.00 Hz 50.00 〇 F00.17 Upper Limit Frequency Control Options 0:
Set through F00.18 1: AI1 2: AI2 3: AI3 4: AI4 (Expansion Card) 5: High-Frequency Pulse Input (X7) 6: Communication Percentage 0 〇