EM600 High-Performance Vector Control Inverter User Manual 60 Function Name of Function Parameter Description Unit Default Property Code Code Setting 7: Communication Direct Setting F00.18 Upper Limit Frequency Lower Limit Frequency F00.19 - Maximum Frequency F00.16 Hz 50.00 ● F00.19 Lower Limit Frequency 0.00 - Upper Limit Frequency F00.18 Hz 0.00 ● F00.20 Running 0:Same; 1: Opposite 0 ● F00.21 Reverse Control 0: permit forward/reverse 1: prohibit reverse 0 〇 F00.22 F/R Deadband Time 0.00 - 650.00 s 0.00 ● F00.23 Carrier Frequency 1.0 - 16.0 (inverter rated power kHz 8.0- 2.0 ● F00.24 Automatic Adjustment of Carrier Wave 0: Disabled 1:
Enabled 1 〇 F00.25 Carrier Frequency Noise Suppression 0: Disabled 1: Enabled 0 〇 F00.26 Noise Suppression Tone 20 - 200 Hz 40 ● F00.27 Noise Suppression Intensity 10 - 150 Hz 100 ● F00.28 Motor Parameter Group Options 0: Motor 1 Parameter 1: Motor 2 Parameter 0 〇 F00.29 User Password 0 - 65535 0 〇 F01 Motor 1 Parameter F01.00 Motor Type 0: Induction Motor 1: Inverter Induction Motor 2: Permanent Magnet Synchronous Motor 0 〇 F01.01 Motor Rated Power 0.10 - 650.00 kW Up To Specific Model 〇 F01.02 Motor Rated Voltage 50 - 2000 V Up To Specific Model 〇