sinee — 6.2 Function Parameter Table

EM600 High-Performance Vector Control Inverter User Manual 76 Function Name of Function Parameter Description Unit Default Property Code Code F06.08 Vector Control Slip Gain 10.00 - 200.00 % 100.00 ● F06.09 Speed Control Torque Lmit Source Selection 0: F06.10 and F06.11 1: AI1 2: AI2 3: AI3 4: AI4 (Expansion Card) 5: Communication (Percentage) 6: Maximum of AI2 and AI3 7: Minimum of AI2 and AI3 0 〇 F06.10 Upper Limit of JOG for Speed Control 0.0 - 250.0 % 165.0 ● F06.11 Upper Limit of Brake Torque for Speed Control 0.0 - 250.0 % 165.0 ● F06.12 Excitation Current Proportional Gain ACR-P1 0.00 - 100.00 0.50 ● F06.13 Excitation Current Integral Time Constant ACR-T1 0.00 - 600.00 0.00:

No Integral ms 10.00 ● F06.14 Torque Current Proportional Gain ACR-P2 0.00 - 100.00 0.50 ● F06.15 Torque Current Integral Time Constant ACR-T2 0.00 - 600.00 0.00: No Integral ms 10.00 ● F06.16 Not Used - - - - F06.17 SVC Zero Frequency Processing Method 0: Brake 1: Normal 2: No Output 2 〇 F06.18 SVC Zero Frequency Band-Type Brake Current 50.0 - 400.0 (100.0=Idling Current) % 100.0 〇 F06.19 Not Used - - - - F06.20 Voltage Feedforward Gain 0 - 100 % 0 ● F06.21 Field Weakening Control Options 0: Disabled 1: Direct Calculation 2: Automatic Adjustment 2 〇