EM600 High-Performance Vector Control Inverter User Manual 75 Function Name of Function Parameter Description Unit Default Property Code Code F05.09 Voltage Rise Time of VF Separation 0.00 - 60.00 s 2.00 ● F05.10 V/F Rotor Voltage Drop Compensation Gain 0.00 - 200.00 % 100.00 ● F05.11 V/F Slip Compensation Gain 0.00 - 200.00 % 100.00 ● F05.12 V/F Slip Filter Time 0.00 - 10.00 s 1.00 ● F05.13 Oscillation Suppression Gain 0 - 20000 100 ● F05.14 Oscillation Suppression End Frequency 0.00 - 600.00 Hz 55.00 ● F05.15 Sagging Control Frequency 0.00 - 10.00 Hz 0.00 ● F05.16 Energy Saving Rate 0.00 - 50.00 % 0.00 ● F05.17 Energy Saving Actuation Time 1.00 - 60.00 s 5.00 ● F05.18 Compensation Gain of Magnetic Flux of Synchronous Motor 0.00 - 500.00 % 100.00 ● F05.19 Filter Time Constant of Magnetic Flux Compensation of Synchronous Motor 0.00 - 10.00 s 0.50 ● F06 Vector Control Parameter Group F06.00 Speed Proportional Gain ASR P1 _ 0.00 - 100.00 12.00 ● F06.01 Speed Integral Time Constant ASR T1 _ 0.000 - 30.000 0.000:
No Integral s 0.200 ● F06.02 Speed Proportional Gain ASR P2 _ 0.00 - 100.00 8.00 ● F06.03 Speed Integral Time Constant ASR T2 _ 0.000 - 30.000 0.000: No Integral s 0.300 ● F06.04 Switching Frequency 1 0.00 - Switching Frequency 2 Hz 5.00 ● F06.05 Switching Frequency 2 Switching Frequency 1 - Maximum Frequency F00.16 Hz 10.00 ● F06.06 Velocity Loop Anti-Saturation Factor 0.000 - 1.000 0.500 ● F06.07 Time Constant of Output Filter of Velocity Loop 0.000 - 0.100 s 0.001 ●