EM600 High-Performance Vector Control Inverter User Manual 74 Function Name of Function Parameter Description Unit Default Property Code Code F04.27 Terminal Start Command Reconfirmation 0: Not to Confirm 1: Confirm 0 〇 F04.28 Not Used - - - - F04.29 Zero Frequency 0.00 - 5.00 Hz 0.25 ● F04.30 Initial Position Search after Power-on or Fault 0: Disabled 1: Enabled 0 ● F05 V/F Control Parameter Group F05.00 V/F Curve Setting 0: Straight V/F 1: Multi-Dot Polyline V/F 2: VF to the 1.3rd 3: VF to the 1.7th 4: Square V/F 5: VF Complete Split Mode (Ud=0, Uq=K*t=Split voltage source voltage) 6:
VF Half-Split Mode (Ud=0, Uq=K*t=F/Fe*2*Split voltage source voltage) 0 〇 F05.01 Multipoint VF Frequency Point F1 0.00 - F05.03 Hz 0.50 ● F05.02 Multipoint VF Voltage Point V1 0.0 - 100.0 (100.0= Motor Rated Voltage) % 1.0 ● F05.03 Multipoint VF Frequency Point F2 F05.01 - F05.05 Hz 2.00 ● F05.04 Multipoint VF Voltage Point V2 0.0 - 100.0 % 4.0 ● F05.05 Multipoint VF Frequency Point F3 F05.03 - Motor Rated Frequency (Reference Frequency) Hz 5.00 ● F05.06 Multipoint VF Voltage Point V3 0.0 - 100.0 % 10.0 ● F05.07 Voltage Source of VF Separation Mode 0: Numeric Setting of VF Separation Voltage 1: AI1 2: AI2 3: AI3 4: High-Frequency Pulse (X7) 5: PID 6: Communication Setting Note:
Motor Rated Voltage is 100%. 0 〇 F05.08 Numeric Setting of VF Separation Voltage 0.0 - 100.0 (100.0= Motor Rated Voltage) % 0.0 ●