sinee — 6.2 Function Parameter Table

EM600 High-Performance Vector Control Inverter User Manual 73 Function Name of Function Parameter Description Unit Default Property Code Code F04.15 S Curve Start Section Time at Acceleration 0.00 - System acceleration time/2 (F15.13=0) 0.0 - System acceleration time/2 (F15.13=1) 0 - System acceleration time/2 (F15.13=2) s 1.00 ● F04.16 S Curve End Section Time at Acceleration 0.00 - System acceleration time/2 (F15.13=0) 0.0 - System acceleration time/2 (F15.13=1) 0 - System acceleration time/2 (F15.13=2) s 1.00 ● F04.17 S Curve Start Section Time at Deceleration 0.00 - System deceleration time/2 (F15.13=0) 0.0 - System deceleration time/2 (F15.13=1) 0 - System deceleration time/2 (F15.13=2) s 1.00 ● F04.18 S Curve End Section Time at Deceleration 0.00 - System deceleration time/2 (F15.13=0) 0.0 - System deceleration time/2 (F15.13=1) 0 - System deceleration time/2 (F15.13=2) s 1.00 ● F04.19 Stop Mode 0:

Ramp-To-Stop 1: Coast-to-Stop 2: Spindle Orientation Enable When Terminal for Running is Disabled 0 〇 F04.20 DC Brake Start Frequency at Stop 0.00 - Maximum Frequency F00.16 Hz 0.00 〇 F04.21 DC Brake Current at Stop 0.0 - 150.0 (100.0= Motor Rated Current) % 100.0 〇 F04.22 DC Brake Time at Stop 0.00 - 30.00, Disabled at 0.00 s 0.00 〇 F04.23 DC Brake Field Weakening Time at Stop 0.00 - 30.00 s 0.50 〇 F04.24 Magnetic Flux Brake Gain 100 – 150 (100: No Magnetic Flux Brake) 100 〇 F04.25 Not Used F04.26 Start Mode after Fault/Coast to Stop 0: Start as per the Set Mode of F04.00 1: Rotation Speed Tracking Start 0 〇