EM600 High-Performance Vector Control Inverter User Manual 78 Function Name of Function Parameter Description Unit Default Property Code Code Current F06.35 Integral Time of High Frequency Range Regulator of Injection Current 0.00 - 300.00 ms 10.00 ● F06.36 Current Loop Proportional Gain of Synchronous Motor 10.00 – 600.00 % 100.00 〇 F06.37 Current Loop Integral Gain of Synchronous Motor 10.00 – 600.00 % 100.00 〇 F06.38 – F06.40 Not Used - - - - F07 Protection Function Setting Group F07.00 Protection Shield - E22 E13 SlU SOU SOC Il P OlP 000 00000 〇 0: Valid Protection 1:
Protection Shielded F07.01 Motor Overload Protection Gain 0.20 - 10.00 1.00 ● F07.02 Motor Overload Pre-Alarming Factor 50 - 100 % 80 ● F07.03 Motor Temperature Sensor Type 0: No Temperature Sensor 1: PT100 2: PT1000 0 ● F07.04 Motor Overheating Protection Threshold 0 - 200 ℃ 110 ● F07.05 Motor Overheating Pre-Alarming Threshold 0 - 200 ℃ 90 ● F07.06 Bus Voltage Control Options 0: Disabled 1: Undervoltage Stall, Enabled 2: Overvoltage Stall, Enabled 3:
Overvoltage Stall and Undervoltage Stall, Enabled 2 〇 F07.07 Overvoltage Stall Control Voltage 110.0 - 150.0 (380V, 100.0=537V) % 128.5 ● F07.08 Undervoltage Stall Control Voltage 60.0 - Judgment Operation Voltage at Power Failure Ending (100.0= Standard Bus Voltage) % 76.0 ● F07.09 Judgment Operation Voltage at Power Failure Ending Undervoltage Stall Control Voltage - 100.0 % 86.0 ●