sinee — 6.2 Function Parameter Table

EM600 High-Performance Vector Control Inverter User Manual 79 Function Name of Function Parameter Description Unit Default Property Code Code F07.10 Judgment Delay Time at Power Failure Ending 0.00 - 100.00 s 5.00 ● F07.11 Current Limit Control 0: Disabled 1: Limit Mode 1 2: Limit Mode 2 2 〇 F07.12 Current Limit Level 20.0 - 180.0 (100.0= Inverter Rated Current) % 150.0 ● F07.13 Rapid Current Limit 0: Disabled 1: Enabled 0 〇 F07.14 Fault Retry Times 0 – 20, 0: Fault Retry Disabled 0 〇 F07.15 Numeric Output Action at Fault Retry 0: Disabled 1:

Enabled 0 〇 F07.16 Fault Retry Interval 0.01 - 30.00 s 0.50 ● F07.17 Recovery Time of Fault Retry Times 0.01 - 30.00 s 10.00 ● F07.18 Fault Retry Ilp HOU HOC SlU SOU SOC **0 00000 〇 0: Permitted 1: Not Permitted F07.19 Action 1 at Fault E21 E16 E15 E14 E13 E12 Olp Ilp 000 00000 〇 0: Coast to Stop 1: Stop as per the Set Stop Mode F07.20 Action 2 at Fault E28 E27 E25 E23 *0000 〇 0: Coast to Stop 1: Stop as per the Set Stop Mode F07.21 Offload Protection 0: Disabled 1: Enabled 0 ● F07.22 Offload Detection Level 0.0 - 100.0 % 20.0 ● F07.23 Load Detection Time 0.0 - 60.0 s 1.0 ● F07.24 Offload Protection 0: Coast to Stop 1:

Stop as per the Set Stop Mode 1 〇 F07.25 Motor Overspeed Detection Level 0.0 - 50.0 (reference frequency is Maximum Frequency F00.16) % 20.0 ● F07.26 Motor Overspeed Detection Time 0.0 - 60.0, 0.0: cancel motor overspeed protection s 1.0 ● F07.27 AVR 0: Disabled 1: Enabled 1 〇 F07.28 Stalling Fault Detection Time 0.0 – 6000.0 (0.0 stalling fault is disabled) s 60.0 〇 F08 Preset Speed and Simple PLC F08.00 Preset Speed 1 0.00 - Maximum Frequency F00.16 Hz 0.00 ●