sinee — 6.2 Function Parameter Table

EM600 High-Performance Vector Control Inverter User Manual 88 Function Name of Function Parameter Description Unit Default Property Code Code 4: 57600 5: 115200 F10.02 Modbus Data Format 0: 1-8-N-1 (1 start bit + 8 data bits +1 stop bit) 1: 1-8-E-1 (1 start bit + 8 data bits + 1 even parity + 1 stop bit) 2: 1-8-O-1 (1 start bit + 8 data bits + 1 odd parity + 1 stop bit) 3: 1-8-N-2 (1 start bit + 8 data bits +2 stop bits) 4: 1-8-E-2 (1 start bit + 8 data bits + 1 even parity +2 stop bits) 5: 1-8-O-2 (1 start bit + 8 data bits + 1 odd parity +2 stop bits) 0 〇 F10.03 Communication Overtime 0.0s - 60.0s, 0.0:

Disabled (also works for master - slave system) s 0.0 ● F10.04 Modbus Response Delay 1 - 20 ms 2 ● F10.05 Master-Slave Communication Function 0: Disabled 1: Enabled 0 〇 F10.06 Master-Slave Options 0: Slave 1: Master (Sent by Broadcast) 0 〇 F10.07 Data Sent by Master 0: Output Frequency 1: Set Frequency 2: Output Torque 3: Set Torque 4: PID Setting 5: Output Current 1 〇 F10.08 Receiving Proportionality Factor of Slave 0.00 - 10.00 (Times) 1.00 ● F10.09 Sending Interval of Master 0.000 - 30.000 s 0.200 ● F10.10 Communication Protocol 0: Modbus-RTU Protocol 1: Profibus-DP Protocol 2: CANopen Protocol 3:

DeviceNet Protocol 0 〇 F10.11 Communication Address of Profibus-DP Expansion Card 1 - 125 1 〇 F10.12 Communication Address of CANopen 1 - 127 1 〇