EM600 High-Performance Vector Control Inverter User Manual 89 Function Name of Function Parameter Description Unit Default Property Code Code Expansion Card F10.13 Communication Address of DeviceNet Expansion Card 0 - 63 1 〇 F10.14 Response Delay Time of Process Data of Communication Card 0.0 - 200.0 ms 0.0 〇 F10.15 Bit Rate of Communication between Expansion Card and Bus Ones Place: CANopen 0: 125K 1: 250K 2: 500K 3: 1M Tens Place: DeviceNet 0: 125K 1: 250K 2: 500K 23 〇 F10.16 PROFIBUS Communication Format 0: PPO1 1: PPO2 2: PPO3 3: PPO4 4: PPO5 × F10.17 Received Data Type PZD2 When the displayed data is 65535, it means that present PZD is not used.
When the displayed data is other data, for example 4609, it means that the function parameter is F18.01 (18D=12H, 01D=01H, 1201H=4609D) 65535 〇 F10.18 Received Data Type PZD3 65535 〇 F10.19 Received Data Type PZD4 65535 〇 F10.20 Received Data Type PZD5 65535 〇 F10.21 Received Data Type PZD6 65535 〇 F10.22 Received Data Type PZD7 65535 〇 F10.23 Received Data Type PZD8 65535 〇 F10.24 Received Data Type PZD9 65535 〇 F10.25 Received Data Type PZD10 65535 〇 F10.26 Received Data Type PZD11 65535 〇