EM600 High-Performance Vector Control Inverter User Manual 99 Function Name of Function Parameter Description Unit Default Property Code Code Induction Motor 75kW) 0.1 - 6000.0 (Motor Rated Power >75kW) Specific Model F14.11 Leakage Inductance of Induction Motor 0.01 - 600.00 (Motor Rated Power ≤ 75kW) 0.001 - 60.000 (Motor Rated Power >75kW) mH Up To Specific Model 〇 F14.12 Mutual Inductance of Induction Motor 0.1 - 6000.0 (Motor Rated Power ≤ 75kW) 0.01 - 600.00 (Motor Rated Power >75kW) mH Up To Specific Model 〇 F14.13 Idling Excitation Current of Induction Motor 0.1 - 600.00 (Motor Rated Power ≤ 75kW) 0.1 - 6000.0 (Motor Rated Power >75kW) A Up To Specific Model 〇 F14.14 Induction Motor Field Weakening Factor 1 10.00 - 100.00 % 87.00 〇 F14.15 Induction Motor Field Weakening Factor 2 10.00 - 100.00 % 80.00 〇 F14.16 Induction Motor Field Weakening Factor 3 10.00 - 100.00 % 75.00 〇 F14.17 Induction Motor Field Weakening Factor 4 10.00 - 100.00 % 72.00 〇 F14.18 Induction Motor Field Weakening Factor 5 10.00 - 100.00 % 70.00 〇 F14.19 Stator Resistor of Synchronous Motor 1 - 60000 (Motor Rated Power ≤ 75kW) 0.1 - 6000.0 (Motor Rated Power >75kW) mΩ Up To Specific Model 〇 F14.20 d-Shaft Inductance of Synchronous Motor 0.01 - 600.00 (Motor Rated Power ≤ 75kW) 0.001 - 60.000 (Motor Rated Power >75kW) mH Up To Specific Model 〇 F14.21 q-Shaft Inductance of Synchronous Motor 0.01 - 600.00 (Motor Rated Power ≤ 75kW) 0.001 - 60.000 (Motor Rated Power >75kW) mH Up To Specific Model 〇 F14.22 Back Electromotive Force of 10.0 - 2000.0 (Back Electromotive Force of Rated Rotation Speed) V Up To Specific 〇