EM630/TC6A Closed-Loop Vector Hoist Inverter User Manual Note: The short-circuit bar relay output terminal wiring between 24V power supply and PLC terminal must be removed, when using an external power supply. The surge voltage absorbing circuit should be installed to drive the inductive load (relay, contactor, etc.), for example RC absorbing circuit (please note that the leakage current should be less than the holding current of the contactor or relay under control), VDR and fly-wheel diode (for DC electromagnetic circuit, please pay attention to the polarity at installation). The component of absorbing circuit should be installed near the two sides of relay or contactor coil. 44 A.
NPN mode with internal power supply (+24Vdc) 24V PLC COM K1 X1 K2 X2 K3 X3 K4 X4 K5 X5 K6 X6 K7 X7 B. PNP mode with external power supply (+24Vdc) 24V PLC COM K1 X1 K2 X2 K3 X3 K4 X4 K5 X5 K6 X6 K7 X7 C. NPN mode with external power supply 24V - + PLC DC 24V COM K1 X1 K2 X2 K3 X3 K4 X4 K5 X5 K6 X6 K7 X7 D. PNP mode with external power supply 24V + - PLC DC 24V COM K1 X1 K2 X2 K3 X3 K4 X4 K5 X5 K6 X6 K7 X7