EM630/TC6A Closed-Loop Vector Hoist Inverter User Manual EM630 A+ + RS485 Communi Host controller OF F GND S 1 GND A- - cation Interface Figure 3–18 Wiring of Single Inverter Communication Interface RS485 terminals of multiple inverters connect to the host controller for communication:
Host RS485 Communication Interface + - GN S 1 Figure 3–19 Wiring of Communication Interfaces of Multiple Inverters Connect to the host controller for communication through RS485/RS232 converter EM630 A+ RS485/ Host RS232 Communicat ion Interface OF F GND A- RS232 Converter S 1 Figure 3–20 Wiring of Communication Interface 3.3.9 Control Circuit Cable and Screw Size The length of the cable for transmitting control signal should be limited to 50m and its distance from the power cable should be greater than 30cm, in order to reduce the interference and attenuation of the control signals. Please use the shielded twisted-pair cable when the analog signals are input externally.
It’s recommended to use 0.5 - 1 mm 2 cable as the control circuit cable. The terminal block of EM630 inverter shall be through control circuit connection terminal. Please use a PH0 cross screwdriver for installation with 46 A GN A- + D OF F EM63 S 0 1 A GN A- + D OF F EM63 S 0 1 A A- + OF F EM63 0