User Guide of EM730 Series Inverter 72 1: Search in the opposite direction if the speed cannot be found in the command direction F04.10 Deceleration time of speed tracking 0.1 - 20.0 s 2.0 〇 F04.11 Speed tracking current 30.0-150.0 (100.0 = rated current of inverter) % 50.0 〇 F04.12 Speed tracking compensation gain 0.00 - 10.00 1.00 〇 F04.14 Acceleration and deceleration mode 0: linear acceleration and deceleration 1: acceleration and deceleration of continuous S curve 2:
acceleration and deceleration of intermittent S curve 0 〇 F04.15 Starting time of S curve in acceleration 0.00~30.00(F15.13=0) 0.0~300.0(F15.13=1) 0~3000(F15.13=2) s 1.00 ● F04.16 Ending time of S curve in acceleration 0.00~30.00(F15.13=0) 0.0~300.0(F15.13=1) 0~3000(F15.13=2) s 1.00 ● F04.17 Starting time of S curve in deceleration 0.00~30.00(F15.13=0) 0.0~300.0(F15.13=1) 0~3000(F15.13=2) s 1.00 ● F04.18 Ending time of S curve in deceleration 0.00~30.00(F15.13=0) 0.0~300.0(F15.13=1) 0~3000(F15.13=2) s 1.00 ● F04.19 Stop mode 0: slow down to stop 1:
free stop 0 〇 F04.20 Starting frequency of DC braking in stop 0.00Hz to maximum frequency F00.16 Hz 0.00 〇 F04.21 DC braking current in stop 0.0~100.0 (100.0 = Rated current of motor) % 50.0% 〇 F04.22 DC braking time in stop 0.00~30.00 0.00: invalid s 0.00 〇 F04.23 Demagnetizati on time for DC braking in stop 0.00 - 30.00 s 0.50 〇