User Guide of EM730 Series Inverter 71 corresponding to 100.00kHz) 13: Communication setting 1 14: count value 15: length value 16: PID output 18: PID feedback 19: PID setting 30: Communication setting 2 F03.27 M1 output bias -100.0~100.0 % 0.0 ● F03.28 M1 output gain -10.000~10.000 1.000 ● F03.31 Control logic options of PLC output terminal D7 D6 D5 D4 D3 D2 D1 D0 0*0 〇 * * * * * R1 * Y1 0: Output 1: no output F03.34 Selection of analog output M1 type 0: 0~10V 1: 4~20mA 2: 0~20mA 0 〇 F04 Start/stop control parameter group F04.00 Start-up method 0: direct start 1:
start of speed tracking 0 〇 F04.01 Start frequency 0.00 - 10.00 Hz 0.00 〇 F04.02 Start frequency hold time 0.00-60.00, 0.00 is invalid s 0.00 〇 F04.03 Starting current of DC braking 0.0~100.0 (100.0 = Rated current of motor) % 100.0 〇 F04.04 Starting time of DC braking 0.00~30.00 0.00: invalid s 0.00 〇 F04.06 Pre-excitation current 50.0-500.0 (100.0 = no-load current) % 100.0 〇 F04.07 Pre-excitation time 0.00 - 10.00 s 0.10 〇 F04.08 Speed tracking mode Ones place: Tracking start frequency 0: maximum frequency 1: stop frequency 2: power frequency Tens place: Selection of search direction 0: search only in command direction 0 〇