sinee — 9.2 Table of functional parameters

User Guide of EM730 Series Inverter 70 69: FDT1 lower limit (pulse) 70: FDT2 lower limit (pulse) 71: FDT1 lower limit (pulse, invalid in JOG) 72: FDT2 lower limit (pulse, invalid in JOG) 73: output overcurrent F03.05 Options of output signal type D7 D6 D5 D4 D3 D2 D1 D0 0*0 〇 * * * * * R1 * Y1 0: level 1: single pulse F03.06 Positive/negative logic of digital output D7 D6 D5 D4 D3 D2 D1 D0 0*0 〇 * * * * * R1 * Y1 0: positive logic, valid in the closed state/invalid in the open state 1: Negative logic, invalid in the closed state/valid in the open state F03.08 Output status control in jog D7 D6 D5 D4 D3 D2 D1 D0 00000 〇 * * * REV FDT2 FDT 1 FAR RUN 0: valid in jogging 1:

invalid in jogging F03.09 Y1 valid delay time 0.000~30.000 s 0.000 ● F03.10 Y1 invalid delay time 0.000~30.000 s 0.000 ● F03.13 R1 valid delay time 0.000~30.000 s 0.000 ● F03.14 R1 invalid delay time 0.000~30.000 s 0.000 ● F03.17 Single pulse time of Y1 output 0.001~30.000 s 0.250 ● F03.19 Single pulse time of R1 output 0.001~30.000 s 0.250 ● F03.21 Options of analog output M1 0: running frequency (absolute value) 1: set frequency (absolute value) 2: output torque (absolute value) 3: set torque (absolute value) 4: output current 5: Output voltage 6: bus voltage 7: output power 8:AI1 9:AI2 12: High-frequency pulse input (with 100% 0 〇