sinee — 9.2 Table of functional parameters

User Guide of EM730 Series Inverter 69 F02.57 AI1 filtering time 0.00 - 10.00 s 0.10 ● F02.58 AI2 filtering time 0.00 - 10.00 s 0.10 ● F02.61 AD hysteresis code 2 - 50 2 〇 F02.62 Selection of analog input AI1 type 0: 0~10V 3: -10~10V 4: 0~5V 0 〇 F02.63 Selection of analog input AI2 type 0: 0~10V 1: 4~20mA 2: 0~20mA 4: 0~5V 0 F02.66 Selection of AI2 current input impedance 0: 500Ω 1: 250Ω 0 〇 F03 Output terminal function group F03.00 Options of Y1 output function 0: no output 1: inverter running (RUN) 2: up to output frequency (FAR) 3: output frequency detection FDT1 4: output frequency detection FDT2 5: reverse running (REV) 6: jog 7: inverter protection 8: inverter ready to run (READY) 9:

reach the upper frequency limit 10: reach the lower frequency limit 11: valid current limit 12: valid overvoltage stall 13: complete simple PLC cycle 14: reach the set count value 15: reach the specified count value 16: Length reached (in meters) 17: motor overload pre-alarm 18: inverter overheat pre-alarm 19: reach the upper limit of PID feedback 20: reach the lower limit of PID feedback 21: analog level detection ADT1 22: analog level detection ADT2 24: undervoltage state 26: up to the set time 27: zero-speed running 38: off-load 47: PLC output 67: Brake control 68: Material cutoff detection output 1 〇 F03.02 Options of R1 output function (EA-EB-EC) 7 〇