sinee — 9.2 Table of functional parameters

User Guide of EM730 Series Inverter 68 F02.32 Options of analog input curve Ones place: Options of AI1 curve 0: curve 1 1: curve 2 2: curve 3 3: curve 4 Tens place: AI2 curve selection 0: curve 1 1: curve 2 2: curve 3 3:

curve 4 10D 〇 F02.33 Minimum input of curve 1 0.00 - F02.35 V 0.10 ● F02.34 Minimum input setting of curve 1 –100.0 - +100.0 % 0.0 ● F02.35 Maximum input of curve 1 F02.33~10.00V V 9.90 ● F02.36 Maximum input setting of curve 1 –100.0 - +100.0 % 100.0 ● F02.37 Minimum input of curve 2 -10.00V~F02.39 V 0.10 ● F02.38 Minimum input setting of curve 2 –100.0 - +100.0 % 0.0 ● F02.39 Maximum input of curve 2 F02.37~10.00V V 9.90 ● F02.40 Maximum input setting of curve 2 –100.0 - +100.0 % 100.0 ● F02.41 Minimum input of curve 3 0.00V - F02.43 V 0.10 ● F02.42 Minimum input setting of curve 3 –100.0 - +100.0 % 0.0 ● F02.43 Input of inflection point 1 of curve 3 F02.41 - F02.45 V 2.50 ● F02.44 Input setting of inflection point 1 of curve 3 –100.0 - +100.0 % 25.0 ● F02.45 Input of inflection point 2 of curve 3 F02.43 - F02.47 V 7.50 ● F02.46 Input setting of inflection point 2 of curve 3 –100.0 - +100.0 % 75.0 ● F02.47 Maximum input of curve 3 F02.45 - 10.00 V 9.90 ● F02.48 Maximum input setting of curve 3 –100.0 - +100.0 % 100.0 ● F02.49 Minimum input of curve 4 -10.00 - F02.51 V -9.90 ● F02.50 Minimum input setting of curve 4 –100.0 - +100.0 % -100.0 ● F02.51 Input of inflection point 1 of curve 4 F02.49 - F02.53 V -5.00 ● F02.52 Input setting of inflection point 1 of curve 4 –100.0 - +100.0 % -50.0 ● F02.53 Input of inflection point 2 of curve 4 F02.51 - F02.55 V 5.00 ● F02.54 Input setting of inflection point 2 of curve 4 –100.0 - +100.0 % 50.0 ● F02.55 Maximum input of curve 4 F02.53 - 10.00 V 9.90 ● F02.56 Maximum input setting of curve 4 –100.0 - +100.0 % 100.0 ●