User Guide of EM730 Series Inverter 76 speed control torque 3: retention 4: retention 5: Communication setting (percentage) 6: the larger of AI1 and AI2 7: The smaller of AI1 and AI2 F06.10 Upper limit of speed control motor torque 0.0 - 250.0 % 165.0 ● F06.11 Upper limit of speed control brake torque 0.0 - 250.0 % 165.0 ● F06.12 Excitation current proportional gain ACR-P1 0.00-100.00 0.50 ● F06.13 Excitation current integral time constant ACR-T1 0.00-600.00 0.00: no integral ms 10.00 ● F06.14 Torque current proportional gain ACR-P2 0.00-100.00 0.50 ● F06.15 Torque current integral time constant ACR-T2 0.00-600.00 0.00: no integral ms 10.00 ● F06.17 SVC zero-frequency processing 0:
braking 1: not processed 2: seal the tube 2 〇 F06.18 SVC zero-frequency braking current 50.0-400.0 (100.0 is the no-load current of the motor) % 100.0 〇 F06.20 Voltage feedforward gain 0 - 100 % 0 ● F06.21 Flux weakening control options 0: Invalid 1: direct calculation 2: automatic adjustment 2 〇 F06.22 Flux 70.00-100.00 % 95.00 ●