sinee — EM730 User Manual

User Manual of EM730/EM730E Series Inverter The PID setting change time refers to the time required for the setting to change from 0.0% to 100.0%, similar to the acceleration and deceleration time function. When the PID setting changes, the actual PID setting will change linearly, thus reducing the impact of sudden changes on the system. Smoothing is invalid during the initial setting. The setting will change from the current feedback value during the start. interference on the feedback, but will cause the decline of the response performance of the F09.22 is used to filter the PID feedback. This is helpful to reduce the impact of process closed-loop system.

F09.23 is used to filter the PID output. This is helpful to reduce the sudden changes in the output frequency of the inverter, but will also cause the decline of the response performance of the process closed-loop system. The function of PID feedback disconnection detection is to prevent galloping caused by feedback disconnection. Depending on the nature of the feedback sensor, the settings are different. If the 0.0% type sensor is fed back at the time of disconnection, the lower limit of PID feedback disconnection detection (F09.25) needs to be set to an appropriate value.

If the feedback amount is below the F09.25 setting and has been maintained for the PID feedback 226 code name setting F09.21 PID setting change time 0.000-30.000 s 0.000 ● Function Function code Default Parameter description Unit Attribute code name setting F09.22 PID feedback filtering time 0.000-30.000 s 0.000 ● F09.23 PID output filtering time 0.000-30.000 s 0.000 ● Function Default setting Function code name Parameter description Unit Attribute code F09.24 Upper limit detection value of PID feedback disconnection 0.00-100.00; 100.00 = invalid feedback disconnection % 100.00 ● F09.25 Lower limit detection value of PID feedback disconnection 0.00-100.00; 0.00 = invalid feedback disconnection % 0.00 ● F09.26 Detection time of PID feedback disconnection 0.000-30.000 s 0.000 ●