User Manual of EM730/EM730E Series Inverter disconnection detection time (F09.26), the PID feedback will be regarded disconnected. When the 100.0% type sensor is fed back at the time of disconnection, the upper limit of PID feedback disconnection detection (F09.24) needs to be set to an appropriate value. If the feedback amount is greater than the feedback amount and has been maintained for the time corresponding to F09.26, the PID feedback will be regarded disconnected. ★ Once the feedback sensor is determined, only the corresponding detection mode can be applied. The upper limit detection and lower limit detection cannot be enabled at the same time.

When the output value and feedback value tend to be stable or the controlled quantity is within the allowable range on some occasions or at a certain moment, and the output is not allowed, the sleep status can be applied for a short time. If the controlled quantity is beyond the control range, the inverter will be awakened and generate the output. These steps will be repeated to make the controlled quantity within the allowable range and also save the energy. The detailed function description is shown in Table 7-17. Table 7-17 Description of Sleep/Wake-up Function 227 Function Function code Default Parameter description Unit Attribute code name setting F09.27 PID sleep control options 0:

Invalid 1: sleep at zero speed 2: sleep at lower frequency limit 3: sleep with tube sealed 0 ● F09.28 Sleep action point 0.00-100.00 (100.00 corresponds to the PID setting feedback range) % 100.00 ● F09.29 Sleep delay time 0.0 - 6500.0 s 0.0 ● F09.30 Wake-up action point 0.00-100.00 (100.00 corresponds to the PID setting feedback range) % 0.00 ● F09.31 Wake-up delay time 0.0 - 6500.0 s 0.0 ● Method Mode of State Description action Positive action (e.g. constant Normal work Judgment of the sleep conditions: If the |Feedback| is greater than the sleep action point (F09.28) (necessary condition:

the feedback pressure must be greater than or equal to the set pressure during restart after the stop or sleep), or the output frequency of the