User Manual of EM730/EM730E Series Inverter F09.37=0: always calculate the integral term This function code does not affect the integral action. F09.37=1: calculate the integral term after the F09.21 set time is reached The integral is unavailable within the first change period (F09.21) after startup. F09.37=2: calculate the integral term when the error is less than F09.38 The integral is unavailable within the first change period (F09.21) after startup. However, the integral will be enabled again if the error is less than F09.38 within this period. F09.39=0: target pressure F09.01* coefficient of wake-up action point F09.40* preset F09.39=1:
wake-up action point (F09.30) The PID will wake up if the value is less than the wake-up point (F09.30) and kept for the wake-up delay time (F09.31). It is dedicated to the water pump application macro. When the overpressure of the pipeline network reaches the value of F09.41 and kept for the set time (F09.42), the E57 pipeline network overpressure protection will be reported. It is dedicated to the straight wire drawing machine of the winding and unwinding application micro. When F27.00 is set to the option 3 (straight wire drawing machine) and the feedback 230 Function Function code Default Parameter description Unit Attribute code name setting F09.39 Wake-up option 0:
target pressure F09.01* coefficient of wake-up action point 1: Wake-up action point (F09.30) 0 〇 F09.40 Coefficient of wake-up action point 0.0-100.0 (100% corresponds to PID setting) % 90.0 ● Function Function code Default Parameter description Unit Attribute code name setting F09.41 Pipeline network alarm overpressure 0.0 to pressure sensor range F09.03 % 90.0 ● F09.42 Overpressure protection time 0-3600 (0: invalid) bar 6 ● Function Function code Default Parameter description Unit Attribute code name setting F09.43 PID reverse limit 0: no limit 1: limit 0 〇