User Manual of EM730/EM730E Series Inverter signal is the maximum value for a long time after startup, the system will be adjusted by PID to the negative output. F09.43=0 : No limit When the output is reduced to 0, it will not be limited and may continue to decrease. F09.43=1: limit When the output is reduced to 0, it will be limited and not continue to decrease. 7.11 Communication Function Parameter Group of F10 Group “single-master multi-slave” communication network with RS-485 bus. The EM730/EM730E series inverter supports the RTU format Modbus protocol, and the For the entire communication network, the inverter as a slave must have its own unique address. Its setting range is 1 to 247.
That is, a network supports 247 slave stations at most. ★ 0 is the broadcast address, which does not need to be set. All slave inverters can be recognized. The slaves and hosts attached to the same network must follow the same sending and receiving principles (e.g. baud rate, data format, and protocol format) to ensure normal communication. Hence, there are three corresponding function codes, i.e. F10.01 (baud rate), F10.02 (data format) and F10.10 (protocol format, Modbus-RTU protocol by default for the EM730/EM730E series inverter). The devices connected to the network must have the same settings.
During the communication based on the Modbus-RTU protocol, the EM730/EM730E series inverter supports six different baud rates in bps (bit/s). Take F10.01=9600bps as an example. It means that data is transmitted at a rate of 9600bits per second. By default, each byte consists of valid 8-bit data (such as 0x01). When 10-bit data needs to be transmitted in the actual 231 Function Default Function code name Parameter description Unit Attribute code setting F10.00 Local Modbus communication address 1-247; 0:
broadcast address 1 〇 Function Function code Default Parameter description Unit Attribute code name setting F10.01 Baud rate of Modbus communication 0:4800 1:9600 2:19200 3:38400 4:57600 5:115200 bps 1 〇