User Manual of EM730/EM730E Series Inverter situation, the transmission time is about 1.04ms (approximately 1.04167ms=10bit/9600bps). In the UART transmission, the data usually consists of a start bit, valid data (8 bits by default), check bit (optional), and a stop bit. The EM730/EM730E series inverter supports six data formats according to the Modbus-RTU combinations in communication. If F10.02=0, it means that the current data consists of one start bit + eight data bits + no check bit + one stop bit. ★ N (NONE): no parity; E (EVEN): even parity; O (ODD), odd parity. response delay during the communication based on the Modbus protocol.
In order to meet different needs, the inverter also supports communication timeout and As shown in Fig. 7-30, the communication time interval △ t is defined as the period from the previous reception of valid data frames by the slave station (inverter) to next reception of valid data frames. If △ t is greater than the set time (depending on the function code F10.03; this function is invalid if set to 0), it will be regarded communication timeout. 232 Function Function Default Parameter description Unit Attribute code code name setting F10.02 Modbus data format 0: 1-8-N-1 (1 start bit + 8 data bits + 1 stop bit) 1: 1-8-E-1 (1 start bit + 8 data bits + 1 even parity check bit + 1 stop bit) 2:
1-8-O-1 (1 start bit + 8 data bits + 1 odd parity check bit + 1 stop bit) 3: 1-8-N-2 (1 start bit + 8 data bits + 2 stop bits) 4: 1-8-E-2 (1 start bit + 8 data bits + 1 even parity check bit + 2 stop bits) 5: 1-8-O-2 (1 start bit + 8 data bits + 1 odd parity check bit + 2 stop bits) 0 〇 Start Bit Valid Data Check Bit Stop Bit 1 7 6 5 4 3 2 1 0 N/O/E 1 Function Function code Default Parameter description Unit Attribute code name setting F10.03 Modbus communication timeout 0.0 to 60.0; 0.0: invalid (also valid for master-slave mode) s 0.0 ●