User Manual of EM730/EM730E Series Inverter Fig. 7-34 Schematic Diagram of Automatic Switching of Acceleration and Deceleration Time During acceleration, if the output frequency is less than the switching frequency of the acceleration time 1 and 2 (F15.11), the acceleration time 1 will be the current valid acceleration time; otherwise, the acceleration time 2 will be the current valid acceleration time. During deceleration, if the output frequency is less than the switching frequency of the deceleration time 1 and 2 (F15.12), the deceleration time 1 will be the current valid deceleration time; otherwise, the deceleration time 2 will be the current valid deceleration time.

Under different working conditions, the acceleration and deceleration time requirements may vary greatly. The system provides three acceleration and deceleration time units, depending on the function code F15.13. F15.13=1 means that the acceleration/deceleration time unit is “0.1s”. Except for that in torque control (F13.06), all the acceleration and deceleration time will change. For example, the value of F00.14 will change from 15.00s to 150.0s by default .

257 Function Parameter description Unit Default Function code name Attribute code setting F15.13 Acceleration and deceleration time unit 0:0.01s 1:0.1s 2:1s 0 〇 Function Default setting Function code name Parameter description Unit Attribute code F15.14 Frequency hopping point 1 0.00-600.00 Hz 600.00 ● F15.15 Hopping range 1 0.00-20.00, 0.00 is invalid Hz 0.00 ● F15.16 Frequency hopping point 2 0.00-600.00 Hz 600.00 ● F15.17 Hopping range 2 0.00-20.00, 0.00 is invalid Hz 0.00 ●