User Manual of EM730/EM730E Series Inverter As shown in Fig. 7-33, the acceleration time is defined as the time of acceleration from 0.00 Hz to the reference frequency of acceleration/deceleration time; and the deceleration time is defined as the time of deceleration from the reference frequency of acceleration/deceleration time to 0.00 Hz. The actual acceleration/deceleration time varies according to the ratio between the set frequency and reference frequency. that represents the reference frequency of acceleration/deceleration time.
If F15.09=0, the The reference frequency of acceleration/deceleration time is set by function code F15.09 reference frequency depends on the function code F00.16 (maximum frequency). Assuming F00.16=100.00Hz, the acceleration (deceleration) time is expressed as the time for the output frequency to increase (decrease) from 0.00Hz (100.00Hz) to 100.00Hz (0.00Hz). If F15.09=2, the reference frequency depends on the function code F18.01 (set frequency). Assuming F18.01=100.00Hz, the acceleration (deceleration) time is expressed as the time for the output frequency to increase (decrease) from 0.00Hz (100.00Hz) to 100.00Hz (0.00Hz). If the motor 1 is running at the normal (e.g.
non-PLC/PID) speed (e.g. non-torque) and the acceleration/deceleration time terminals (19: acceleration and deceleration time terminal 1; 20: acceleration and deceleration time terminal 2) are invalid, the acceleration/deceleration time 1 and acceleration/deceleration time 2 can be switched by setting F15.10 to 1, as detailed in Fig. 7-34. 256 Function Parameter Default Function code name Unit Attribute code description setting F15.10 Automatic switching of acceleration and deceleration time 0: Invalid 1:
valid 0 〇 F15.11 Switching frequency of acceleration time 1 and 2 0.00 to maximum frequency F00.16 Hz 0.00 ● F15.12 Switching frequency of deceleration time 1 and 2 0.00 to maximum frequency F00.16 Hz 0.00 ●