User Manual of EM730/EM730E Series Inverter D = 50% to 60% for lifting equipment with a lowering height over 100m The recommended power and resistance for the braking resistor of the EM730/EM730E series inverter are given in the table below. The recommended resistor power is calculated based on the braking rate (10% to 20%). It is for reference only. If the inverter is used in the case of frequent acceleration/deceleration or continuous braking, the power of the braking resistor needs to be increased. The user can change the value according to the load conditions, but within the specified range. ★ The wires listed above refer to the outgoing wires of a single resistor.

If resistors are connected in parallel, the bus should be enlarged accordingly. The withstand voltage of the wires should be AC300V or above for the single-phase model and AC450V or above for the three-phase model. Cables should be resistant to 105 ℃ . 10.2 Braking unit For the EM730/EM730E series inverters (EM730/EM730E-045-3 and above), use our BR100 series braking units (power range: 18.5-160kW). The models of our braking units are as follows.

314 Wire (mm2) Motor Resistance Resistor Power Inverter Model Connected to (kW) (Ω) (W) Resistor EM730/EM730E-0R4-2B 0.4 ≧360 ≧200 1 EM730/EM730E-0R7-2B 0.75 ≧180 ≧400 1.5 EM730/EM730E-1R5-2B 1.5 ≧180 ≧400 1.5 EM730/EM730E-2R2-2B 2.2 ≧90 ≧800 2.5 EM730/EM730E-0R7-3B 0.75 ≧360 ≧200 1 EM730/EM730E-1R5-3B 1.5 ≧180 ≧400 1.5 EM730/EM730E-2R2-3B 2.2 ≧180 ≧400 1.5 EM730/EM730E-4R0-3B 4 ≧90 ≧800 2.5 EM730/EM730E-5R5-3B 5.5 ≧60 ≧1000 4 EM730/EM730E-7R5-3B 7.5 ≧60 ≧1000 4 EM730/EM730E-011-3B 11 ≧30 ≧2000 6 EM730/EM730E-015-3B 15 ≧30 ≧2000 6 EM730/EM730E-018-3B 18.5 ≧30 ≧2000 6 EM730/EM730E-022-3B 22 ≧15 ≧4000 6 EM730/EM730E-030-3B 30 ≧10 ≧4000 6 EM730/EM730E-037-3B 37 ≧10 ≧6000 6