User Manual of EM730/EM730E Series Inverter ★ When BR100-160 works with the minimum resistance, the braking unit can work continuously at the braking frequency D=33%. In the case of D>33%, intermittent operation will be performed; otherwise, the over-temperature protection will be enabled. 10.2.1 Selection of Connecting Wires Since all braking units and braking resistors work at high voltage (>400VDC) and in the discontinuous status, please select appropriate wires. See Table 4-29 for the wiring specifications of the main circuit. Use the cables with the conforming insulation levels and cross-sections.

Table 4-29 Wire Specifications of Braking Units and Braking Resistors Flexible cables have higher flexibility. Because cables may be in contact with high-temperature devices, it is recommended to use copper-core and heat-resistant flexible cables or flame-retardant cables. The braking unit should be close to the inverter as much as possible and no more than 2m far away from the inverter. Otherwise, the DC-side cables should be twisted and used with magnetic rings to reduce radiation and inductance. in Fig. 4-19.

The lengths of connecting wires of the braking unit, braking resistor and inverter are shown 315 Minimum Applicable Model and Average Braking Peak Current Application Resistance Inverter Power specification Current I (A) av I (A) max (Ω) (kW) BR100-045 Energy consumption braking 10 45 75 18.5 - 45 BR100-160 Energy consumption braking 6 75 150 55 - 160 Specification Average Braking Peak Braking Current Cross-section (mm2) of and model Current I (A) av I (A) max Copper-core Cable BR100-045 45 75 10 BR100-160 75 150 16 BR100-315 120 300 25