sinee — EM730 User Manual (EN)

User Manual of EM730/EM730E Series Inverter 98 action point F09.41 Pipeline network alarm overpressure 0.0 to pressure sensor range F09.03 % 90.0 ● F09.42 Overpressure protection time 0-3600 (0: invalid) bar 6 ● F09.43 PID reverse limit 0: no limit 1: limit 1 〇 F10 Communication function group F10.00 Local Modbus communicati on address 1-247; 0: broadcast address 1 〇 F10.01 Baud rate of Modbus communicati on 0:4800 1:9600 2:19200 3:38400 4:57600 5:115200 1 〇 F10.02 Modbus data format 0: 1-8-N-1 (1 start bit + 8 data bits + 1 stop bit) 1: 1-8-E-1 (1 start bit + 8 data bits + 1 even parity check bit + 1 stop bit) 2: 1-8-O-1 (1 start bit + 8 data bits + 1 odd parity check bit + 1 stop bit) 3:

1-8-N-2 (1 start bit + 8 data bits + 2 stop bits) 4: 1-8-E-2 (1 start bit + 8 data bits + 1 even parity check bit + 2 stop bits) 5: 1-8-O-2 (1 start bit + 8 data bits + 1 odd parity check bit + 2 stop bits) 0 〇 F10.03 485 communicati on timeout 0.0s-60.0s; 0.0: invalid (valid for the master-slave mode) s 0.0 ● F10.04 Modbus response delay 1 - 20 ms 2 ● F10.05 Options of master-slave communicati on function 0: Invalid 1: valid 0 〇 F10.06 Master-slave options 0: slave 0 〇