sinee — EM730 User Manual (EN)

User Manual of EM730/EM730E Series Inverter 99 1: host (Modbus protocol broadcast transmission) F10.07 Data sent by host 0: output frequency 1: set frequency 2: output torque 3: set torque 4: PID setting 5: output current 1 〇 F10.08 Proportional factor of slave reception 0.00-10.00 (multiple) 1.00 ● F10.09 Host sending interval 0.000-30.000 s 0.200 ● F10.10 Communicati on protocol option 0: Modbus-RTU protocol 0 × F10.56 Options of 485 EEPROM writing 0-10: default operation (for commissioning) 11: writing not triggered (available after commissioning) 0 〇 F10.57 Enabling of SCI sending timeout resetting 0:invalid resetting 1:

valid resetting 1 ● F10.58 Delay time of SCI sending timeout resetting 110~10000 mS 150 ● F10.59 SCI response option 0: Reply to both read and write commands 1: Reply to write commands only 2: No reply to both read and write commands 0 〇 F11 User-selected parameter group F11.00 User-selected parameter 1 The displayed content is Uxx.xx, which means that the Fxx.xx function code is selected When the function code F11.00 is enabled, the keyboard displays U00.00, indicating that the first selected parameter is F00.00.

U00.00 ● F11.01 User-selected parameter 2 U00.01 ● F11.02 User-selected parameter 3 U00.02 ● F11.03 User-selected parameter 4 U00.03 ● F11.04 User-selected parameter 5 U00.04 ● F11.05 User-selected U00.07 ●