User’s Guide for EM760 series high-performance vector inverter 80 F12.39 LCD large-line display parameter 2 0.00~99.99 18.06 ● F12.40 LCD large-line display parameter 3 0.00~99.99 18.01 ● F12.41 Options of UP/DOWN zero crossing 0: prohibit zero crossing 1:

allow zero crossing 0  F12.42 Frequency setting of digital potentiometer 0.00 to maximum frequency 00.16 HZ 0.00 × F12.43 Digital potentiometer torque setting 0.00-|Digital torque setting F13.02| % 0.0 × F12.46 ACLib version number XXX.XX × F12.45 UP/DOWN function selection Cha nnel shari ng Scop e Limi t Key boar d Com mun icati on High -spe ed puls e Anal og quan tity Digi tal freq uenc y Mult i-seg ment spee d 00100010  0 0 1 0 0 0 1 0 0: Invalid 1: valid F12.47 Any address 0~65535 28673 ● F13 Torque control parameter group F13.00 Speed/torque control options 0: Speed control 1: Torque control 0  F13.01 Options of torque setting source 0: digital torque setting F13.02 1: AI1 2: AI2 3:

AI3 4: AI4 (expansion card) 5: high frequency pulse input (X7) 6: Communication setting (Full range of the items 1-6, corresponding to F13.02 digital torque setting) 0  F13.02 Digital torque setting -200.0 to 200.0 (100.0 = the rated torque of motor) % 100.0 ● F13.03 Multi-segment torque 1 -200.0~200.0 % 0.0 ● F13.04 Multi-segment torque 2 -200.0~200.0 % 0.0 ● F13.05 Multi-segment torque 3 -200.0~200.0 % 0.0 ● F13.06 Torque control acceleration and deceleration time 0.00~120.00 s 0.05 ● F13.08 Upper frequency limit options of torque control 0: set by F13.09 1: AI1 2: AI2 3: AI3 4: AI4 (expansion card) 5: high frequency pulse input (X7) 0 