User’s Guide for EM760 series high-performance vector inverter 81 6: Communication setting (percentage) 7: Communication setting (direct frequency setting) F13.09 Upper frequency limit of torque control 0.00 to maximum frequency F00.16 Hz 50.00 ● F13.10 Upper frequency limit offset 0.00 to maximum frequency F00.16 Hz 0.00 ● F13.11 Static friction torque compensation 0.0~100.0 % 0.0 ● F13.12 Frequency range of static friction compensation 0.00~50.00 Hz 1.00 ● F13.13 Dynamic friction torque compensation 0.0~100.0 % 0.0 ● F13.18 Reverse speed limit options 0~100 % 100 ● F13.19 Speed priority enabling of torque control 0: Disable 1:
Enable 0 ● F14 Motor 2 parameter group (for details, refer to the user's manual or the complete function table) F15 Auxiliary function group F15.00 Jog frequency 0.00 to maximum frequency F00.16 Hz 5.00 ● F15.01 Jog acceleration time 0.00~650.00 (F15.13=0) 0.0~6500.0 (F15.13=1) 0~65000 (F15.13=2) s 5.00 ● F15.02 Jog deceleration time s 5.00 ● F15.03 Acceleration time 2 s 15.00 ● F15.04 Deceleration time 2 s 15.00 ● F15.05 Acceleration time 3 s 15.00 ● F15.06 Deceleration time 3 s 15.00 ● F15.07 Acceleration time 4 s 15.00 ● F15.08 Deceleration time 4 s 15.00 ● F15.09 Fundamental frequency of acceleration and deceleration time 0: maximum frequency F00.16 1: 50.00Hz 2:
set frequency 0 F15.10 Automatic switching of acceleration and deceleration time 0: Invalid 1: valid 0 F15.11 Switching frequency of acceleration time 1 and 2 0.00 to maximum frequency F00.16 Hz 0.00 ● F15.12 Switching frequency of deceleration time 1 and 2 0.00 to maximum frequency F00.16 Hz 0.00 ● F15.13 Acceleration and deceleration time unit 0:0.01s 1:0.1s 2:1s 0 F15.14 Frequency hopping point 1 0.00~600.00 Hz 600.00 ● F15.15 Hopping range 1 0.00~20.00, 0.00: Invalid Hz 0.00 ● F15.16 Frequency hopping point 2 0.00~600.00 Hz 600.00 ●