User’s Guide for EM760 series high-performance vector inverter 82 F15.17 Hopping range 2 0.00~20.00, 0.00: Invalid Hz 0.00 ● F15.18 Frequency hopping point 3 0.00~600.00 Hz 600.00 ● F15.19 Hopping range 3 0.00~20.00, 0.00: Invalid Hz 0.00 ● F15.20 Detection width of output frequency arrival (FAR) 0.00~50.00 Hz 2.50 F15.21 Output frequency detection FDT1 0.00 to maximum frequency F00.16 Hz 30.00 F15.22 FDT1 hysteresis -(Fmax-F15.21)~F15.21 Hz 2.00 F15.23 Output frequency detection FDT2 0.00 to maximum frequency F00.16 Hz 20.00 F15.24 FDT2 hysteresis -(Fmax-F15.23)~F15.23 Hz 2.00 F15.25 Options of analog level detection ADT 0: AI1 2: AI3 1: AI2 3:
AI4 (expansion card) 0 F15.26 Analog level detection ADT1 0.00~100.00 % 20.00 ● F15.27 ADT1 hysteresis 0.00 to F15.26 (valid down in one direction) % 5.00 ● F15.28 Analog level detection ADT2 0.00~100.00 % 50.00 ● F15.29 ADT2 hysteresis 0.00 to F15.28 (valid down in one direction) % 5.00 ● F15.30 Options of energy consumption braking function 0: Invalid 1: valid 0 F15.31 Energy consumption braking voltage 110.0~140.0 (380V,100.0=537V) % 128.5 F15.32 Braking rate 20-100 (100 means that duty ratio is 1) % 100 ● F15.33 Operating mode with set frequency less than lower frequency limit 0: running at the lower frequency limit 1: Shutdown 2:
zero-speed running 0 F15.34 Fan control Ones place: Fan control mode 0: running after power-on 1: running at startup 2: intelligent operation, subject to temperature control Tens place: Electrification fan control 0: Run 1 minute first and then enter the fan control mode for running 1: Directly run in the fan control mode Hundreds place: Low-speed fan running mode enabled (above 200kW) 0: Low-speed running invalid 1: Low-speed running valid 101 F15.35 Overmodulation intensity 1.00~1.10 1.05 ●