U.S. Department of Defense MIL-HDBK-704-3 — NOT MEASUREMENT

Downloaded from https://www.everyspec.com MIL-HDBK-704-3 True RMS Frequency Spectrum Oscilloscope Voltmeter Counter Power Meter Analyzer Distortion Meter (See Note 4) (See Note 4) (See Note 4) (See Note 4) (See Note 4) (See Note 4) (UUT) Adjustable AC 3-Phase A B N 8 Power Supply See Note 2 IF USED N (See Note 6) CHASSIS See Note 3 10 cm GND CAUTION Ground Plane Notes: 1. Voltage measurements shall be made within 10 cm of UUT input power terminals. 2. For 3 phase 4 wire equipment, neutral connection to also be made within 10 cm of UUT Stimulation & Monitoring input power terminals.

For 3 phase 3 wire equipment, line-to-neutral measurements to be made with neutral connection made to power supply neutral. Equipment (See Note 5) 3. CAUTION: Verify suitability of power supply NEUTRAL and GROUND connections. 4. CAUTION: Verify suitability of instumentation inputs and/or use appropriate attenuation. 5. Stimulation and Monitoring Equipment are user defined. This functional block shall provide appropriate inputs (stimulations) and monitor UUT outputs (e.g.: RPM, signals, data, etc.) Load Measurements 6. If current waveform limits are imposed by the detail performance specification, the AC Figure TAC101-1 power source shall be a rotating machine. FIGURE TAC101-1.

Load measurement. Current Transformers 3X See Note 1