Downloaded from https://www.everyspec.com MIL-HDBK-704-3 TABLE TAC102-I. MIL-STD-704 normal limits for steady state voltage, voltage unbalance, and frequency. 1/ Normal steady state frequency limits for MIL-STD-704B for helicopters is 400 +20 Hz. 3. Apparatus. The test equipment should be as follows: a. Adjustable AC power supply b. True RMS voltmeter c. Frequency counter 4. Test setup. Configure the test setup as shown in figure TAC102-1. Measurements, except current, must be made within 10 cm of the input power terminals of the UUT. 5. Compliance test. With the power source off, install the UUT and the stimulation and monitoring equipment into the test setup of figure TAC102-1.
Turn on the power source and adjust the voltage to the nominal steady state voltage of 115 Vrms (line-to-neutral) and adjust the frequency to the nominal steady state frequency of 400 Hz. Energize the UUT. Allow sufficient time for the UUT to warm up. Conduct a performance test of the UUT according to the utilization equipment performance test procedures to verify that the UUT is providing specified performance for normal aircraft electrical conditions.
For each test condition A through K noted in table TAC102-II, the UUT must remain for a length of time that confirms the utilization equipment can continuously operate at the steady state voltage and frequency limits and should be not less than thirty (30) minutes. Test conditions A through I are three phase balanced voltages. Test conditions J and K are unbalanced voltage conditions. At each test condition conduct a performance test of the UUT according to the utilization equipment performance test procedures to verify that the UUT is providing specified performance for normal aircraft electrical conditions. For each test condition shutdown the UUT and verify that the UUT can be re-started.
After re-start conduct a performance test of the UUT according to the utilization equipment performance test procedures to verify that the UUT is providing specified performance for normal aircraft electrical conditions. Record the voltages, frequency, time duration at test condition, successful/unsuccessful re-start and the performance of the UUT for each test condition in the data sheet shown in table TAC102-III. Repeat for each mode of operation of the UUT.
11 Normal Limit 704A 704B 704C 704D 704E 704F Voltage NLSS 108 V 108 V 108 V 108 V 108 V 108 V Voltage NHSS 118 V 118 V 118 V 118 V 118 V 118 V Voltage Unbalance 3.0V 3.0V 3.0V 3.0V 3.0V 3.0V Frequency NLSS 380 Hz 395 Hz 1/ (380 Hz) 393 Hz 393 Hz 393 Hz 393 Hz Frequency NHSS 420 Hz 405 Hz 1/ (420 Hz) 407 Hz 407 Hz 407 Hz 407 Hz