Downloaded from https://www.everyspec.com MIL-HDBK-802 (SH) 2 July 1990 6.2.3 Spiraling the cable run to minimize the effects of unequal current division. A dc circuit cable run array consisting of multiple, single-conductor cables will be spiraled (twisted) on itself from one cable hanger to the next Even when the greatest of care is exercised to ensure equal current division, absolute equality is difficult to obtain and maintain in low resistance parallel circuits such as those involved in minesweeping cable runs.
Unequal heating of the cables, for example, will cause differences in the temperatures and resistances of the conductors connected in parallel and corresponding differences in the currents they carry. Spiraling the cable run on itself provides a way to minimize the effects of such inequality in current division. Cable runs less than 1.5 meters long need not be spiraled. NOTES : 1. Cable arrangement figures illustrate the cross-sectional views of the single conductor cables in a cable run "+" indicates positive conductor cables connected in parallel. ‘-” indicated negative conductor cables connected in parallel.
For a given arrangement, if all “+” are changed to “-” and all “-” are changed to “+”, the same indicated maximum flux density will result. The indicated maximum flux density is the vertical component calculated on a plane 7. 5 meters above or below the cable run based upon cables with an outside diameter of 40 mm that are touching FIGURE 46. Arrangement of single-conductor dc cables for opposing current loops. 85