Downloaded from https://www.everyspec.com MIL-HDBK-802(SH) 2 July 1990 will be preferred for dc power cable connections. We will avoid cable runs consisting of only one or an odd multiple of single-conductor cables in the positive and negative branches of a dc circuit. This is because an odd number of current loops makes magnetic field compensation by arrangement of the conductors impracticable and results in a large magnetic field. 6.2.2.1.2 Use of double-conductor cables. If four single-conductor, quadded cable is unavailable or not practicable, we may use double-conductor cable in a dc cable run.

It will be twisted such that the cable’s conductors are transposed at regular intervals by the twist of the conductors to form the lay of the cable or the conductors are concentric and the size of the cable is small enough to be handled conveniently for the selected application. 6.2.2.1.3 Arrangement of cables for opposing current loops. We will arrange parallel, single-conductor cables in the positive and negative branches of a dc cable run in a manner that will result in opposing (subtractive) current loops, so that their magnetic fields are opposed and self-compensating.

Figure 46 illus- trates typical cable arrangements that are preferred and nonpreferred and gives their respective magnetic flux density values. 6.2.2,1.4 Equal current division among cables connected in parallel. We will select and install parallel, single-conductor cables in the positive and negative branches of a dc cable run so that the resistance of each branch circuit in parallel is as nearly equal as possible in order for the circuit current to divide equally among all of the conductors connected in parallel. Figure 47 illus- trates the effects of unequal current division in cables connected in parallel. 6.2.2.1.5 Unequal current division in double-conductor cables.

We will not connect two or more double-conductor cables in parallel dc cable runs since unequal division of current between conductors connected in parallel can give rise to a magnetic field of objectionable magnitude, If we have a positive conductor in one cable carrying 1,100 amperes (A) and the negative conductor carrying 900 A, while in the other cable the positive conductor carries 900 A and the negative carries 1,100 A, we have an arrangement that is equivalent to two single conductor cables each carrying 200 A.

The center-to-center distance between the cables will be considerable because of the size of the cables, and the magnetic field produced by such a division of current will be considerable. This is the reason why double conductor cables connected in parallel should not be used in minesweeping cable runs. 6.2.2.2 AC newer cables. Design considerations for ac power cables will be in accordance with 5.2.2.2.1 through 6.2.2.2.2. 6.2.2.2.1 Phase conductors in a common cable. We need not be concerned with special cable arrangements if all phase conductors of an ac circuit are in the same cable. 6.2.2.2.2 Phase conductors in separate cable .

If we find it necessary to install ac phase conductors in separate cables, these cables will not be grouped on the same cable hangers with cables carrying dc and they will be as close together as practicable throughout the entire length of the cable run Closed loops of magnetic material around a phase conductor cable and the placement of any magnetic q aterial between the phase conductor cables will be avoided. 84