NAVSEA MIL-HDBK-802(SH) — MIL-HDBK-802(SH) Design of Electrical Equipment with Small Stray Magnetic Fields Manual PDF

Downloaded from https://www.everyspec.com MIL-HDBK-802(SH) 2 July 1990 6.2.3.4 Other numbers of cables. Any even number of cables spiraled about a central core with the cables alternately plus and minus will produce a small stray magnetic field. For convenient connection to three-terminal equipment the number of cables will be an integral multiple of four because one-half of the cables must be connected to the central terminal and one-fourth of the cables to each of the two outer terminals. An adapter between the cable run and the equipment will be required if the number of cables is not an integral multiple of four.

This does not mean that the number of cables in the cable run must be an integral multiple of four. It is conceivable that generator rating and available cable sizes might be so related that four cables vould not be enough, six just right, and eight more than enough. In such a case it would be desirable not to throw out six cables immediately in favor of eight, but to make a fairly detailed comparison between a six cable run with adapters and an eight cable run without adapters. We might discover that the overall advantage might be with the six cable run. 6.2.4 Cable spacing.

Equality between two opposing current loops can be disturbed by inequality of current division, a condition that we have already considered, or by inequality in cable spacing. Suppose we have a quad array in which the upper two cables are spaced farther apart than the lower two. In this case the upper and lower current loops will not be of equal strength, and the principle of zero net magnetic moment (see 5 5) will not be satisfied even if the loop currents are equal.

If we want to avoid the magnetic field that would be produced by opposing loops of unequal strength, we must arrange the cables in a quad arrangement so that the cables are pressed tightly together all along the cable run, with their centers at the corners of a square In a circular array of cables arranged about a central core, we must have the cables equally spaced. This condition will be automatically satisfied if the cables are all of the same diameter, the central core is of the right diameter, and the cables are tightly clamped against the core. Figure 50 illustrates the typical effects of excessive cable separation in a quad arrangement. 89