Downloaded from https://www.everyspec.com MIL-HDBK-802(SH) 2 July 1990 (c) A single concentric cable co carry the current from the largest minesweeping generator will be large in diameter, difficult to manufacture, and inconvenient to install. Therefore, the present view is that the minesweeping cable runs now in use are satisfactory and that we do not need to use concentric cable. 6.3 Connections between equipment and cable runs. The design considerations for connections between equipment and cable runs will be in accordance with 6 3.1 through 6.3.4.7. 6.3.1 Compatibility of cable runs and terminal.

In accordance with the principle of compatibility (see 5.10), we will arrange terminals on equipment for ready connection to the cable runs that take current to and from the equipment. In the absence of a terminal arrangement to which the cable run can be conveniently connected, we will use adapters between the cable run and the equipment . 6.3.2 Arrangement of terminals and approach by cable run. Terminals for cable runs will be equally spaced, parallel terminals in the same plane arranged edgewise (see 6.3.4.1) or flat (see 6,3,4.3) with the cable run approaching the terminals endways (see 6.3.4.3), crossways (see 6.3,4.2), or sideways (see 6.3.4.5).

Edgewise terminals are preferred since the center-to-center distance between terminals can be made smaller than for flat terminals, which results in smaller current loops. Edgewise terminals can use the same type of cable lugs as endways and crossways connections. 6.3.3 Cable runs. We will usually have four, single-conductor cables in a cable run. However, on occasion there will be eight single-conductor cables in a cable run, and it is conceivable that it may be advantageous to use a different number in other cases (see 6.2.6.5). 6.3 4 Three-terminal arrangements. We will make cable connections to three- terminal arrangements in accordance with 6.3.4.1 through 6.3.4.7.

We will orient the cable run approach either endways, crossways or sideways (see figure 51). If the terminals rotate into some other plane, or in some other orientation in the same plane, the endways, crossways, and sideways directions for cable connections will rotate with the terminals.