Downloaded from https://www.everyspec.com MIL-HDBK-802 (SH) 2 July 1990 6.3.4.3 Four-cable connection with endways approach to flat terminals We will connect a four, single-conductor cable run approaching endways to flat terminals in accordance with figure 54. Cable lugs used for edgewise terminals can be used with flat terminals. NOTES: 1. The cable run will approach the terminals with its axis in line with 2. horizontal axis of the center terminal T2, The two cables 2 and 4, which lie in a vertical plane, will be bolted to the upper and lower sides of terminal, T2. Cable 1 will be bent to the left and slightly down to be bolted to the 3. under side of terminal T1.
Cable 3 will be bent to the right and slightly up to the upper side of terminal T3. The area outlined by cables 1 and 4 equals the area outlined by cables 2 4. and 3. The polarity of the current in the loop made by cables 1 and 4 is opposite to the polarity of the current in the loop made by cables 2 and 3. 5. FIGURE 54. Connection of an endways cable run with four cables to flat terminals. 95