NAVSEA MIL-HDBK-802(SH) — MIL-HDBK-802(SH) Design of Electrical Equipment with Small Stray Magnetic Fields Manual PDF

Downloaded from https://www.everyspec.com MIL-HDBK-802(SH) 2 July 1990 6.3.4.4 Four-cable connection with crossways approach to flat terminals. We will connect a four, single-conductor cable run approaching crossways to flat terminals in accordance with figure 55. With flat terminals, different types of cable lugs will have to be used for crossways connections rather than those used with edgewise connections. NOTES: 1. The cable run will approach the terminals with its axis in line with vertical axis of the center terminal T2. The two cables 2 and 4, which lie in a vertical plane, will be bolted to the upper side of terminal, T2.

Cable 1 will be bent to the left and slightly forward to be bolted to the 2. 3. upper side of terminal T1. Cable 3 will be bent to the right and slightly back to the upper side of terminal T3. The area outlined by cables 1 and 4 equals the area outlined by cables 2 4. and 3. The polarity of the current in the loop made by cables 1 and 4 is oppo- site to the polarity of the current in the loop made by cables 2 and 3. 5. FIGURE 55. Connection of a crossways cable run with four cables to flat terminals. 96