Downloaded from https://www.everyspec.com MIL-HDBK-802 (SH) 2 July 1990 6.4.2.2 Conductors lying in the same plane on each side of the bend. We can also bend the basic conductor arrangement so that the conductors lie in the same plane both before and after the bend (see figure 62). The conductor arrangement creates opposing current loops of equal area so that the condition of zero net magnetic moment is satisfied. This arrangement is difficult to accomplish in practice. Consequently , we preferred the use of conductor bends lying in different planes on each side of the bend for power circuit arrangements of disconnect switch boxes and contactor panels. FIGURE 62.
Bend for conductors lying in the same plane on each side of the bend. 6.4.3 Parallel compensation. The basic conductor arrangement we have considered makes use of parallel compensation (see 5.6.1.1.2). Zero net magnetic moment in parallel compensation is dependent upon equality of current division between two (or more) conductors in parallel. Absolute equality of current division is difficult to ensure in low resistance circuits; hence, in order to be safe it will be necessary to add refinement to the basic conductor arrangement, which will guarantee that the magnetic field will not be greatly increased if nominally equal currents actually depart somewhat from exact equality.
6.4.4 Current loops in power circuits, We will keep the size of current loops created by the power circuits as small as possible to minimize the magnetic moments of the current loops. The distance between these current loops will also be minimized. Conductor and device separation will be kept to the minimum. 6.4.5 Terminals. Three terminals are necessary for connection of a basic conductor arrangement. Most of the equipment we will use will be three terminal devices; however, some are two terminal devices. A generator needs only one set of three terminals.
A disconnect switch or contactor panel needs two sets of three terminals, one set to connect the incoming cable run and one set to connect the outgoing cable run. 103