Downloaded from https://www.everyspec.com 6 4.8 Folded arrangement, The folded arrangement for disconnect switch boxes and contactor panels will be the preferred arrangement. We will use this arrangement in all cases except where special circumstances make it indispensable or highly advantageous to have a disconnect switch box or contactor panel with incoming and outgoing terminals at opposite ends of the box or panel. The folded arrangement inherently requires the incoming and outgoing terminals to be at the same end of the box or panel.

Actual separation of conductors will be the minimum required to meet the applicable electrical creepage and clearance distances specified for the disconnect switch box. 6.4.8.1 Folded arangement for disconnect switch box. The design considerations for the folded arrangement for a disconnect switch box will be in accordance with 6.4.8.1.1 through 6.4.8.1.4. 6.4.8.1.1 Description of connection. Using a straight through arrangement, we will spread the overload relay and shunt apart longitudinally, and then bend the bus work between them through two right angles so that the components are folded upon each other (see figure 65). FIGURE 65. Folded arrangement for a disconnect switch box. 107