Downloaded from https://www.everyspec.com MIL-HDBK-802(SH) 2 July 1990 6.4.8.1.2 Advantages. The folded arrangement is a refinement of the straight-through arrangement in that the effect of unequal current division between parallel circuits is almost eliminated. The folded arrangement (see figure 65) has six current loops, A, B, C, D, E, and F. We will design the disconnect switch box so that loops A, B, C, and D are all equal in area and the area of E is equal to the area of F. 6.4 8.1.3 Equal current loops.
If the current is the same in the outer conductors of the disconnect switch box, loops A, B, C, and D will be of equal strength, A and D producing a magnetic field directed down, B and C a magnetic field directed up. The resultant field from these four loops will be small. Loops E and F will be of equal strength and opposite polarity. The resultant field from these two loops will be small. Therefore, the resultant magnetic field from all six loops together will be small 6.4.8.1.4 Unequal current loops. Suppose that the current is unequally divided between the two outer conductors.
Loops A, B, C, and D will no longer be of equal strength, but A will still be equal to B since the same current flows in both, and C will be equal to D The resultant field of loops A, B, C, and D will be small because A is equal and opposite to B, and C is equal and opposite to D Loops E and F will, however, no longer be equal and opposite. Their resultant field will be approximately equal to that of a single loop with an area equal to that of loop E or F, and a current equal to the difference between the currents in the two outer conductors. However, the area of loops E and F in the folded arrangement is much less than the area of the two loops in the straight-through arrangement.
Therefore, the effect of unequal current division will be correspondingly less than for the straight-through arrangement. 6.4.8.2 Folded arrangement for contactor panel. We will form the contactor panel equipment into a folded arrangement (see figure 66). The design should be such that current loops A, B, C and D are equal in area and as small and as close together as feasible. If the current division is equal or unequal the external magnetic field will be small No matter how we divide the current, loop A is equal and opposite to loop B since they are of equal area and carry the same current. The same is true of loops C and D.
The net magnetic moment for loops A, B, C, and D is, therefore, equal to zero regardless of whether the current is equally divided between the two outer conductors or not. The sum of the currents in loops E and G is always equal to the current in loop F no matter how we divide the current between loops E and G. Therefore, the net magnetic moment for loops E, F, and G is equal to zero whether the current is equally divided between the two outer conductors or not. Loops H and I, however, will not be balanced in the case of unequal current division, but the areas of the loops can be made very small by putting the bus bars across the bottom of the contactor panel very close together.
If this is done, the magnetic field from the contactor panel should be small for either equal or unequal division of current between the outer conductors . 108