Downloaded from https://www.everyspec.com MIL-HDBK-802(SH) 2 July 1990 (i) Coils. Coils of the same kind (shunt field coils, commutating field coils, and so forth) will be of the same size and shape and have the same number of turns. Some engine-starting motors have series field coils with different number of turns on the different poles . Such a construction is unacceptable for motors or generators intended for use on a minesweeper. Even when care is used to make a machine as uniform and symmetrical as possible, there will inevitably be slight departures from this desired condition.
It is believed that the equalizer connections on the armature will operate to minimize the effects of certain sources of nonuniformity. These connections and their function are discussed in detail in 7.3.2.9. Here, it will suffice to say chat they function to strengthen weak poles and weaken strong poles, hence, to smooth out and equalize the main field flux distribution. They should, therefore, tend to minimize the effects of such causes of nonuniformity as difference in air gaps and field coils that are not of exactly equal magnetic q oment because of manufacturing tolerances.
On the other hand, it is possible that the equalizer connections would not do much, if anything, to minimize the effects of lack of symmetry caused by the presence of magnetic feet outside the frame of the generator. 7.2.3.5 Minimum number of poles in minesweeping generators. We have seen in 7.2.3.1 that the polar leakage field is decreased by increasing the number of field poles, other things remaining the same. This raises the question of what is the minimum number of field poles permissible in minesweeping generators that must have a low stray magnetic field.
The answer is to be obtained only by a detailed study of each particular case, taking into account the size of the generator and the stringency of the magnetic field limits it has to meet. The following guidelines are to be kept in mind: (a) Two poles are never enough. (b) Four and six poles are doubtful Until we have more information than we have at present, neither four nor six poles should be used for minesweeping generators. (c) Eight poles should be enough, but for the largest machines more would be better. 7.2.3.6 Minimum number of poles in other generators and in motors.
The problem is even more complicated for these than for minesweeping generators because of the great range in size involved. For a small machine, the magnetic moments of the field coils and their distances from the center of the machine will be less than for a large machine. Both effects will tend to give a smaller stray magnetic field and it should not be necessary to have as many poles as on a minesweeping generator. (a) Two-pole motors or generators should never be used on minesweepers except in very small sizes, 100 watts input or output or less. Even for the very small machines it would be better to have four poles.
The two-pole machine is completely different from machines with four or more poles. In the two-pole machine, the magnetic fields produced by the two field poles are necessarily additive. 127