Downloaded from https://www.everyspec.com FIGURE 77. Currents the conductors in the armature circuit of a four-pole generator with two brush collector ring. 7.3.2.7 Isolation of armature currents. We now have the values of the currents in all the conductors visible on figure 75 and have determined them for the general case in which the four sets of brushes do not take equal currents. It must be remembered, however, that the conductors shown on figure 75 are not the only ones with which we are concerned. In addition to these, there are other conductors that will be perpendicular to the plane of the paper, and therefore will be invisible in the developed view of figure 75.
These invisible conductors are the commutator risers that connect the commutator to the armature winding at points 1, 2, 3, and 4, and the connections from the brushes to the brush collector rings at points 6, 8, 9, and 10. The invisible conductors will be considered later, For the time being, we will confine our attention to the currents in the conductors that are visible on figure 75. Even with this restriction, it is not easy to visualize the magnetic field that will be produced by the conductors that are visible on figure 75.
To understand this magnetic field, we turn our atten- tion from the currents in the conductors to the system of current loops that will give the same current distribution and produce the same magnetic field. We then break the system of current loops down into several groups that are individually small enough to digest. The first step in this process is the transition from figure 75 to figure 77. Comparison of these figures shows that they are the same everywhere except along a line connecting points 1, 2, 3, and 4, Figure 75 shows that there is no direct (straight line) connection between points 1 and 2; hence, no current flowing directly between these points.
On figure 77, however, there is a direct connection between these points The current in this connection is immediately adjacent to an equal and opposite current, so the net current, which flows directly between points 1 and 2, is zero, just as on figure 75. Similalar considerations apply to the connections that run directly between points 2 and 3, 135