Перечни параметров Руководство по программированию привода VLT ® HVAC Basic Drive 5.1.6 4-** Пределы/ Предупреждения 5 5 Таблица 5.7 5.1.7 5-**Цифровой вход/ выход Таблица 5.8 MG18B250 - VLT ® является зарегистрированным товарным знаком Danfoss 103 Par. No.
# Parameter description Default value 2-set-up Change during operation Conver- sion index Type 4-1* Motor Limits 4-10 Motor Speed Direction [2] Both directions All set-ups FALSE - Uint8 4-12 Motor Speed Low Limit [Hz] 0.0 Hz All set-ups FALSE -1 Uint16 4-14 Motor Speed High Limit [Hz] 65.0 Hz All set-ups FALSE -1 Uint16 4-18 Current Limit 110.0% All set-ups TRUE 0 Uint16 4-19 Max Output Frequency 65.0 Hz All set-ups FALSE -1 Uint16 4-5* Adj.
Warnings 4-50 Warning Current Low 0.00 A All set-ups TRUE -2 Uint32 4-51 Warning Current High 194.00 A All set-ups TRUE -2 Uint32 4-58 Missing Motor Phase Function [1] On All set-ups FALSE - Uint8 4-6* Speed Bypass 4-61 Bypass Speed From [Hz] 0.0 Hz All set-ups TRUE -1 Uint16 4-63 Bypass Speed To [Hz] 0.0 Hz All set-ups TRUE -1 Uint16 4-64 Semi-Auto Bypass Set-up [0] Off All set-ups TRUE - Uint8 Par. No.
# Parameter description Default value 2-set-up Change during operation Conver- sion index Type 5-0* Digital I/O mode 5-00 Digital Input Mode [0] PNP 1 set-up FALSE - Uint8 5-03 Digital Input 29 Mode [0] PNP 1 set-up FALSE - Uint8 5-1* Digital Inputs 5-10 Terminal 18 Digital Input [8] Start All set-ups TRUE - Uint8 5-11 Terminal 19 Digital Input [0] No operation All set-ups TRUE - Uint8 5-12 Terminal 27 Digital Input [2] Coast inverse All set-ups TRUE - Uint8 5-13 Terminal 29 Digital Input [14] Jog All set-ups TRUE - Uint8 5-4* Relays 5-40 Function Relay ExpressionLimit All set-ups TRUE - Uint8 5-9* Bus Controlled 5-90 Digital & Relay Bus Control 0.0 N/A All set-ups TRUE 0 Uint32