mg — MG18B250 VLT HVAC Basic Drive Руководство по программированию

Перечни параметров Руководство по программированию привода VLT ® HVAC Basic Drive 5.1.8 6-** Аналоговый вход/ выход 5 5 Таблица 5.9 104 MG18B250 - VLT ® является зарегистрированным товарным знаком Danfoss Par. No.

# Parameter description Default value 2-set-up Change during operation Conver- sion index Type 6-0* Analog I/O Mode 6-00 Live Zero Timeout Time 10.0 s All set-ups TRUE 0 Uint8 6-01 Live Zero Timeout Function [0] Off All set-ups TRUE - Uint8 6-1* Analog Input 53 6-10 Terminal 53 Low Voltage 0.07 V All set-ups TRUE -2 Uint16 6-11 Terminal 53 High Voltage 10.0 V All set-ups TRUE -2 Uint16 6-12 Terminal 53 Low Current 4.0 mA All set-ups TRUE -2 Uint16 6-13 Terminal 53 High Current 20.0 mA All set-ups TRUE -2 Uint16 6-14 Terminal 53 Low Ref./Feedb. Value 0.0 N/A All set-ups TRUE -3 Int32 6-15 Terminal 53 High Ref./Feedb.

Value 50.0 N/A All set-ups TRUE -3 Int32 6-16 Terminal 53 Filter Time Constant 0.01 s All set-ups TRUE -2 Uint16 6-19 Terminal 53 mode [1] Voltage mode 1 set-up TRUE - Uint8 6-2* Analog Input 54 6-20 Terminal 54 Low Voltage 0.07 V All set-ups TRUE -2 Uint16 6-21 Terminal 54 High Voltage 10.0 V All set-ups TRUE -2 Uint16 6-22 Terminal 54 Low Current 4.0 mA All set-ups TRUE -2 Uint16 6-23 Terminal 54 High Current 20.0 mA All set-ups TRUE -2 Uint16 6-24 Terminal 54 Low Ref./Feedb. Value 0.0 N/A All set-ups TRUE -3 Int32 6-25 Terminal 54 High Ref./Feedb.

Value 50.0 N/A All set-ups TRUE -3 Int32 6-26 Terminal 54 Filter Time Constant 0.01 s All set-ups TRUE -2 Uint16 6-29 Terminal 54 mode [1] Voltage mode 1 set-up TRUE - Uint8 6-7* Analog/Digital Output 45 6-70 Terminal 45 Mode [0] 0-20 mA All set-ups TRUE - Uint8 6-71 Terminal 45 Analog Output [0] No operation All set-ups TRUE - Uint8 6-72 Terminal 45 Digital Output [0] No operation All set-ups TRUE - Uint8 6-73 Terminal 45 Output Min Scale 0.0% All set-ups TRUE -2 Uint16 6-74 Terminal 45 Output Max Scale 100.0% All set-ups TRUE -2 Uint16 6-76 Terminal 45 Output Bus Control 0.0% All set-ups TRUE -2 Uint16 6-9* Analog/Digital Output 42 6-90 Terminal 42 Mode [0] 0-20 mA All set-ups TRUE - Uint8 6-91 Terminal 42 Analog Output [0] No operation All set-ups TRUE - Uint8 6-92 Terminal 42 Digital Output [0] No operation All set-ups TRUE - Uint8 6-93 Terminal 42 Output Min Scale 0.0% All set-ups TRUE -2 Uint16 6-94 Terminal 42 Output Max Scale 100.0% All set-ups TRUE -2 Uint16 6-96 Terminal 42 Output Bus Control 0.0% All set-ups TRUE -2 Uint16