127 Electromagnetic Compatibility The shielding performance of a cable is indicated by its transfer impedance Z T . The transfer impedance relates a current on the surface of the shield to the voltage drop generated by this current on the opposite surface of the shield: U2 I1 Fig. 5.6 Illustration of transfer impedance Z T = , where L is the cable length U 2 I 1 • L The lower the transfer impedance value the better the shielding performance. The table below shows typical values of transfer impedance for diff erent kinds of motor cable. The most common type of motor cable is the single layer braided copper wire as it off ers a good shielding performance at a reasonable price.
Aluminium foil with copper drain wir Twisted copper wires or steel wire armoured cable Single layer braided copper wire – with various percantages of screen coverage Dual layer braided copper wire Dual layer braided copper wire with high permeable middle layer Cable runs in rigid copper or steel conduit Fig. 5.7 Shielding performance of diff erent cable types