Power supply unit (PSU) К Push the lock spring inward to unlock the CMA stopper (see figure 39 ). V CAUTION! In case of not enough space at the under side, unlock the CMA stopper of the server below and pull out the CMA to the rear side. К Remove the CMA stopper with the mounted crossbar (see figure 40 ). К Hold the CMA stopper, the crossbar and the CMA including cables in the one hand. К Remove the FJBU and install the dummy cover carefully. К Mount the complete assembly (CMA stopper, the crossbar and the CMA) again into the rail. 6.3.2.1 Preliminary steps К No steps needed. 6.3.2.2 Removing an FJBU Figure 46: Removing an FJBU К Press in on the green locking latch (1).

К While keeping the green locking latch pressed, pull the FJBU out of its bay (2). V CAUTION! Never leave the bay for the FJBU empty. Install a new FJBU or install the dummy cover. RX2530 M4 Upgrade and Maintenance Manual 125